
by type:
or model number:
If the model is not available, please contact us directly for advice.
Wiring Diagrams
Use & Care Manuals
Product Briefs
This comprehensive range of Smoke and Heat alarms is designed to operate with suitable 8-30volt control panels and to provide a loud local alarm. Relay contacts (normally open and closed supplied) are available for triggering the panel itself and its associated ancillary products, such as extra loud sirens, magnetic door holders, etc. Battery back-up ensures that the units are always powered, even during a power failure. Additionally, the alarms can be interconnected so that when one senses fire, all the units located throughout the premises sound.
Dual ionisation chamber – quick response to fast flaming fires
Power supply voltage 10.5 – 30VDC
Alkaline Battery backup
Low battery warning
Built in sounder to give a sound output of minimum 85dB(A) at 3m
Interconnectable with up to 20 smoke/heat alarms
Relay operates in continuous or pulse mode
Relay contacts rated at 30VDC/1 AMP
Manual Test button to test detector circuitry, sounder, relay and activate all interconnected alarms
Hush button to silence nuisance alarms
Green LED power indicator to confirm panel power supply
Circular Easi-Fit mounting base for quick installation
Fully tested and approved
5 Year guarantee (limited)
For full Installation and Siting Instructions please refer to the Use and Care Manual
Ideally install in the centre of ceiling at least 300mm(1ft) from light fittings. Keep ionisation alarms away from kitchens to prevent nuisance alarms. Interconnect all alarms
Remove unit from mounting plate by releasing catch
Check battery is connected to snap. Battery will not power the unit until it is snapped on to the mounting plate
Ensure the panel is correctly connected to all terminals otherwise the units will not operate correctly. Check green panel power light is lit on mounting plate
Do not fit actual alarm until all building work is completed to avoid contamination. After checking operation, cover smoke alarm with dust cover until required for use
Frequent nuisance Alarms occur:
Close kitchen/bathroom door when in us
Ensure that the alarm is sited at least 6m away from sources of fumes
Contamination from insects, paint or paint fumes may have occured. Clean the alarm
If the problem persists, resiting of the unit should be considered. Alternatively, replace the unit with an Optical unit(Ei186/185), assuming that the problem is with an Ionisation type alarm(Ei181/180)
Alarm sounds for no apparent reason:
Identify the alarm source. On interconnected units, the red light on the cover will flash rapidly only on the unit which is the source of the alarm
Check for fumes, steam etc. from the kitchen or bathroom. Paint and other fumes can cause nuisance alarms
Press the test/hush button to silence the Smoke/Heat Alarm for 10 minutes
If the alarm does not stop, remove the unit.(Only remove alarm with red light flashing, the others are probably satisfactory)
Low battery & other beeps:
If the battery is correctly connected and the unit has beeped for over 20 minutes the battery is probably depleted. Obtain a new battery, remove the alarm and replace the depleted battery
If the panel is providing power and replacing battery or cleaning unit has not stopped beeps, a fault may exist. Replace the unit
The Ionisation/Heat(Ei181/184) units give two beeps 10 minutes after the test/hush button is pressed
If the Optical unit (Ei186) beeps without the red light flashing at the same time, the chamber is defective. Clean the chamber
Interconnected Alarms do not all sound and the relay does not switch:
Hold test button for 10 seconds after first alarm has sounded to ensure signal is transmitted to all units. Relay should switch
Check that the green power light on the mounting plate is on
Check panel and wiring